| Approvals/certifications |
Certified to EN54-7 by the LPCB. |
| Compatibility |
Compatible with C-TEC’s XFP/ZFP XP95/Discovery Addressable Fire Panels. |
| Application/operation |
Uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm. Very good at detecting flaming high heat fires. |
| Application temperature |
n/a |
| Static response temperature |
n/a |
| Supply wiring |
2-wire, polarity insensitive. |
| Supply/operating voltage |
17 to 28V DC. |
| Quiescent current |
280µA average; 500µA peak. |
| Alarm current |
2mA (LED illuminated). |
| Indicators |
Clear LED emitting red light when in alarm. |
| Connections |
L1&L2 supply in/out; R remote LED Ve connection; -R remote LED -Ve connection. (4mA remote LED current @ 5V measured across remote load). |
| Product dimensions (mm) |
100mm diameter x 42 mm H (not in base). 50mm height when in base. |
| Construction & finish |
White polycarbonate V.O rated rated to UL94. Stainless steel terminals. |
| IP Rating |
IP23D. |
| Weight |
105g (not in base); 161g (in base). |
| Operating conditions/temperature |
-20ºC to 60ºC. |
| Notes |
Requires a BF308XP standard base or BF308XPR low power relay base. 1mA power up surge current for 0.3 seconds. |