| Approvals/certifications |
LPCB certified to EN54-5 & 17 and Kiwa Telefication certified to EN54-13. |
| Compatibility |
Compatible with C-TEC’s XFP/ZFP CAST Protocol Addressable Fire Panels. |
| Type |
Class A1R, Class A2 or Class B Heat (Programmable). |
| Application/operation |
Generates an alarm when a specific temperature is reached (Modes 1, 2 & 3). In Mode 1 also generates an alarm when a sudden rise in temp is detected. |
| Sensitivity |
Mode 1 (A1R): Rate of Rise and 56ºC fixed; Mode 2 (A2): 62ºC fixed; Mode 3 (B): 74ºC fixed. Selectable at the panel. |
| Supply wiring |
2-wire, polarity sensitive. |
| Supply/operating voltage |
22 to 40V DC. |
| Quiescent current |
370µA typical @ 22 to 40V DC. |
| Alarm current |
5mA typical (LEDs illuminated) @ 22 to 40V DC. |
| Indicators |
2 LED indicator strips emitting red light when in alarm offering 360º visibility. Optional remote LED. |
| Connections |
Via CA408 base: 1 +Ve IN (analogue swich); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen. |
| Product dimensions (mm) |
102.2mm diameter x 37mm deep (detector only); 102.2mm diameter x 57.5mm deep (detector in base). |
| Construction & finish |
White polycarbonate casing rated to UL94 V-2 with nylon parts. |
| IP Rating |
IP42. |
| Weight |
99g (not in base); 154g (in base). |
| Operating conditions/temperature |
-20ºC to +85ºC. |
| Notes |
Requires a CA408 CAST base. CA408R relay base also available. |